RATINGS
CONTINUOUS CURRENT
SYSTEM VOLTAGE
SYSTEM FREQUENCY
SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (TIME BASED)
SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (SPECIFIC FUSE CLASS)
SHORT-TIME WITHSTAND AND CLOSE-ON (TIME-BASED)
STANDARDS
THIRD PARTY APPROVAL/RECOGNITION
NEMA
SEISMIC QUALIFICATION
EMISSIONS
ELECTROMAGNETIC COMPATIBILITY (EMC)
DEVICES
CIRCUIT PROTECTION
SAFETY
SURGE PROTECTION
POWER AND ENERGY METERS
ENCLOSURE
ENCLOSURE TYPE
ACCESS
CABLE ENTRY
MOUNTING (CATALOG DEPENDENT)
Up to 5000 A
Up to 600 Vac
50/60 Hz
100kA (0.05 sec)
200 kA
85kA (0.5 sec)
UL 1008 and CSA 22.2 No. 178 Listed
1, 3R
IBC, CBC, UBC Zone 4, OSHPD
FCC Part 15 (Subpart B); CISPR 11
IEC 61000-4-2: electrostatic discharge immunity
IEC 61000-4-3: radiated immunity
IEC 61000-4-4: fast transient/burst immunity
IEC 61000-4-5: surge immunity
IEC 61000-4-6: conducted immunity
IEC 61000-4-11: voltage dip/interruption immunity
Magnum DS Low Voltage Power Circuit Breaker
Arcflash Reduction Maintenance System
Surge Protective Devices
Power Xpert, IQ Meters
Indoor & outdoor
Rear (standard), Front (optional)
Top/bottom
Floor
 LOW-VOLTAGE SOLUTIONS
Overview
Technical
Resources
RATINGS CONTINUOUS CURRENTUp to 5000 A
SYSTEM VOLTAGEUp to 600 Vac
SYSTEM FREQUENCY50/60 Hz
SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (TIME BASED)100kA (0.05 sec)
SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (SPECIFIC FUSE CLASS)200 kA
SHORT-TIME WITHSTAND AND CLOSE-ON (TIME-BASED)85kA (0.5 sec)
STANDARDS THIRD PARTY APPROVAL/RECOGNITIONUL 1008 and CSA 22.2 No. 178 Listed
NEMA1, 3R
SEISMIC QUALIFICATIONIBC, CBC, UBC Zone 4, OSHPD
EMISSIONSFCC Part 15 (Subpart B); CISPR 11
ELECTROMAGNETIC COMPATIBILITY (EMC)IEC 61000-4-2: electrostatic discharge immunity
IEC 61000-4-3: radiated immunity
IEC 61000-4-4: fast transient/burst immunity
IEC 61000-4-5: surge immunity
IEC 61000-4-6: conducted immunity
IEC 61000-4-11: voltage dip/interruption immunity
Magnum DS Low Voltage Power Circuit Breaker
SAFETYArcflash Reduction Maintenance System
SURGE PROTECTIONSurge Protective Devices
POWER AND ENERGY METERSPower Xpert, IQ Meters
ENCLOSURE ENCLOSURE TYPEIndoor & outdoor
ACCESSRear (standard), Front (optional)
CABLE ENTRYTop/bottom
MOUNTING (CATALOG DEPENDENT)Floor