RATINGS
CONTINUOUS CURRENT

Up to 5000 A

SYSTEM VOLTAGE

Up to 600 Vac

SYSTEM FREQUENCY

50/60 Hz

SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (TIME BASED)

100kA (0.05 sec)

SHORT-CIRCUIT WITHSTAND AND CLOSE-ON (SPECIFIC FUSE CLASS)

200 kA

SHORT-TIME WITHSTAND AND CLOSE-ON (TIME-BASED)

85kA (0.5 sec)

STANDARDS
THIRD PARTY APPROVAL/RECOGNITION

UL 1008 and CSA 22.2 No. 178 Listed

NEMA

1, 3R

SEISMIC QUALIFICATION

IBC, CBC, UBC Zone 4, OSHPD

EMISSIONS

FCC Part 15 (Subpart B); CISPR 11

ELECTROMAGNETIC COMPATIBILITY (EMC)

IEC 61000-4-2: electrostatic discharge immunity
IEC 61000-4-3: radiated immunity
IEC 61000-4-4: fast transient/burst immunity
IEC 61000-4-5: surge immunity
IEC 61000-4-6: conducted immunity
IEC 61000-4-11: voltage dip/interruption immunity

DEVICES
CIRCUIT PROTECTION

Magnum DS Low Voltage Power Circuit Breaker

SAFETY

Arcflash Reduction Maintenance System

SURGE PROTECTION

Surge Protective Devices

POWER AND ENERGY METERS

Power Xpert, IQ Meters

ENCLOSURE
ENCLOSURE TYPE

Indoor & outdoor

ACCESS

Rear (standard), Front (optional)

CABLE ENTRY

Top/bottom

MOUNTING (CATALOG DEPENDENT)

Floor